Thermal Calculation for Facades
A step-by-step thermal calculation from profile section to curtain wall module: 2D model, Uf and psi, Uw and Ucw, condensation check and report, with worked examples in 7 days.
Before you start
Who is it for
Facade and window designers and engineers who prepare thermal calculations and energy reports.
What you need
- Basic facade physics (Facade Physics, in Turkish)
- A 2D thermal bridge program (e.g. the free THERM)
- Profile sections as DXF
Programme
| Day | Topic | What you learn | Time |
|---|---|---|---|
| Day 1 | Basics | λ, R, U, psi; spandrel example; U-values on a facade; national requirements | ~3.5 h |
| Day 2 | Uw | EN ISO 10077-1 formula, example window, sensitivity | ~3.5 h |
| Day 3 | 2D model | Geometry, λ values, air cavities, boundary conditions | ~3.5 h |
| Day 4 | Uf | Calculation with an insulation panel, example, checks | ~3.5 h |
| Day 5 | ψg | Real glass and spacer, example, spacer types | ~3.5 h |
| Day 6 | Ucw and condensation | Component method, example module, fRsi, dew point | ~3.5 h |
| Day 7 | Report | Tools, report sections, common mistakes, final exercise | ~3.5 h |
Each day ends with a checklist. Your ticks are saved in this browser. If you only study on weekday evenings, the course takes about two weeks. Example values are for teaching. For official calculations use the current editions of the standards, national requirements and the project specification.
Basics
Goal
By the end of the day you will know the basics of heat transfer (λ, R, U, Rsi, Rse), the names of the U-values used for facades (Ug, Uf, Up, Uw, Ucw, ψ), the standards behind them and where national requirements fit in. About 3 hours.
About this course: a step-by-step thermal calculation for facade and window sections: U-values by hand, Uw with EN ISO 10077-1, 2D numerical frame calculation (Uf, ψ) with EN ISO 10077-2, curtain walls with EN ISO 12631, and condensation checks. Background: Facade Physics (in Turkish). Values in the examples are for teaching; for an official calculation use the current editions of the standards and the project specification. Terms are in the glossary.
1. Basic concepts (1 hour)
| Symbol | Meaning | Unit |
|---|---|---|
| λ (lambda) | Thermal conductivity of the material | W/(m·K) |
| d | Thickness | m |
| R = d / λ | Thermal resistance of a layer | m²·K/W |
| Rsi, Rse | Internal and external surface resistances | m²·K/W |
| U = 1 / Rtotal | Thermal transmittance (heat through 1 m² per 1 K difference) | W/(m²·K) |
| ψ (psi) | Linear thermal transmittance (extra loss per 1 m of length) | W/(m·K) |
For a plain layer: U = 1 / (Rsi + Σ d/λ + Rse). For horizontal heat flow (walls, facades) the usual values are Rsi = 0.13 and Rse = 0.04 m²·K/W.
2. Example: spandrel panel (45 min)
100 mm mineral wool (λ = 0.035) and thin metal sheets (their resistance is ignored):
U = 1 / (0.13 + 0.10 / 0.035 + 0.04) = 1 / (0.13 + 2.857 + 0.04) = 1 / 3.027 = 0.33 W/(m²·K)
This is the value at the centre of the panel. The aluminium frames and connections at the edges are thermal bridges; the real value of the facade is calculated together with them (day 6).
3. U-values on a facade (45 min)
| Symbol | Of what | How it is found |
|---|---|---|
| Ug | Centre of glass | EN 673 (from the glass manufacturer) |
| Up | Centre of the opaque panel | By hand (as above) |
| Uf | Frame profile | EN ISO 10077-2 numerical calculation or test (day 4) |
| ψg, ψp | Frame-glass and frame-panel junctions | EN ISO 10077-2 numerical calculation (day 5) |
| Uw | Window | EN ISO 10077-1 (day 2) |
| Ucw | Curtain wall | EN ISO 12631 (day 6) |
4. National requirements (15 min)
Limit values for facade components come from national rules (for example TS 825 in Turkey, the national energy regulations in EU countries). Find which climate zone your project is in and what the code requires for windows and curtain walls.
End-of-day check (15 min)
Uw
Goal
By the end of the day you will be able to calculate a window's Uw value with EN ISO 10077-1 from areas, the glazing perimeter and ψ. About 3 hours.
1. Formula (45 min)
Uw = (Ag·Ug + Af·Uf + lg·ψg) / (Ag + Af)
| Symbol | Meaning |
|---|---|
| Ag | Visible glass area |
| Af | Frame area (projected) |
| lg | Visible glass perimeter |
| ψg | Extra loss where the glass edge (spacer) meets the frame |
Areas and lengths are taken from the visible sizes (whichever of the inside or outside is larger); check the measuring rules of the standard.
2. Example (1 hour)
Window 1230 × 1480 mm with a 100 mm visible frame on every side; Ug = 1.1, Uf = 2.0 W/(m²·K), ψg = 0.06 W/(m·K):
| Item | Calculation | Value |
|---|---|---|
| Aw | 1.23 × 1.48 | 1.8204 m² |
| Ag | 1.03 × 1.28 | 1.3184 m² |
| Af | Aw − Ag | 0.5020 m² |
| lg | 2 × (1.03 + 1.28) | 4.62 m |
| Ag·Ug | 1.3184 × 1.1 | 1.4502 W/K |
| Af·Uf | 0.5020 × 2.0 | 1.0040 W/K |
| lg·ψg | 4.62 × 0.06 | 0.2772 W/K |
| Uw | 2.7314 / 1.8204 | 1.50 W/(m²·K) |
3. What matters most? (45 min)
| Change | New Uw |
|---|---|
| Ug 1.1 → 0.7 (triple glazing) | (0.9229 + 1.004 + 0.2772) / 1.8204 = 1.21 |
| Uf 2.0 → 1.4 | (1.4502 + 0.7028 + 0.2772) / 1.8204 = 1.33 |
| ψg 0.06 → 0.035 (warm edge spacer) | (1.4502 + 1.004 + 0.1617) / 1.8204 = 1.44 |
In small windows the frame and edge effects grow; in large glazing Ug dominates.
4. Tables or calculation? (15 min)
EN ISO 10077-1 also gives table values for Uf and ψ; they are on the safe (pessimistic) side. Better values for a real profile require a 2D numerical calculation (days 3-5) or a test.
End-of-day check (15 min)
2D model
Goal
By the end of the day you will be able to model a profile section for a 2D numerical thermal calculation: geometry, materials, air cavities and boundary conditions. About 3.5 hours.
1. Why 2D? (30 min)
In a profile section, aluminium, the thermal break (polyamide), gaskets and air cavities sit side by side; heat finds the easiest path. That is why Uf and ψ are calculated with a 2D finite element model of the section (EN ISO 10077-2). The standard also gives example sections for validating software (validation cases); check that your program solves them correctly.
2. Geometry (45 min)
- Take the section as DXF (from the system supplier's catalogue or your own drawing).
- Simplify unnecessary detail: screw holes, very small fillets.
- Turn every region into a closed area (polygon) with no overlaps and no gaps.
3. Materials (45 min)
Typical thermal conductivities (W/(m·K); take exact values from the standard or the manufacturer):
| Material | λ |
|---|---|
| Aluminium alloy | 160 |
| Steel | 50 |
| Stainless steel | 17 |
| Polyamide with 25 % glass fibre (thermal break) | 0.30 |
| EPDM gasket | 0.25 |
| Silicone | 0.35 |
| Glass | 1.0 |
| Insulation panel (for the Uf calculation) | 0.035 |
Aluminium conducts about 530 times better than polyamide: the width and continuity of the thermal break decide Uf.
4. Air cavities (45 min)
- Closed cavities: modelled as a solid with an equivalent thermal conductivity given by the method in the standard, depending on the cavity size and temperature difference (convection and radiation included).
- Slightly ventilated cavities (with small openings to the outside) and ventilated cavities are treated separately in the standard.
- The program may do this automatically, but you decide which cavity is which type.
5. Boundary conditions (30 min)
| Surface | Temperature | Surface resistance |
|---|---|---|
| Inside | θi = 20 °C | Rsi = 0.13 m²·K/W (normal) |
| Inside, corners and recesses | 20 °C | Rsi = 0.20 m²·K/W (where radiation and convection are reduced) |
| Outside | θe = 0 °C | Rse = 0.04 m²·K/W |
| Cut edges | — | Adiabatic (no heat flow) |
End-of-day check (15 min)
Uf
Goal
By the end of the day you will be able to calculate Uf according to EN ISO 10077-2: insulation panel instead of glass, 2D heat flow, subtracting the panel contribution. About 3 hours.
1. Method (1 hour)
- Remove the real glass; put an insulation panel of the same thickness (λ = 0.035) in its place.
- The visible width of the panel must be bp ≥ 190 mm (so that the edge effect dies out).
- Solve the model → Lf2D: the total heat through the section per 1 K temperature difference (W/(m·K)).
- Subtract the panel's contribution:
Uf = (Lf2D − Up · bp) / bf
| Symbol | Meaning |
|---|---|
| Lf2D | Thermal coupling coefficient from the 2D calculation |
| Up | U-value of the insulation panel (by hand) |
| bp | Visible panel width |
| bf | Visible (projected) frame width |
2. Example (1 hour)
28 mm panel, bp = 0.19 m, bf = 0.08 m, Lf2D = 0.40 W/(m·K) from the program:
| Step | Calculation | Result |
|---|---|---|
| Up | 1 / (0.13 + 0.028 / 0.035 + 0.04) = 1 / 0.97 | 1.031 W/(m²·K) |
| Up · bp | 1.031 × 0.19 | 0.196 W/(m·K) |
| Lf2D − Up·bp | 0.40 − 0.196 | 0.204 W/(m·K) |
| Uf | 0.204 / 0.08 | 2.55 W/(m²·K) |
3. Checks (45 min)
- Temperature distribution (isotherms): they should crowd in the thermal break; the inner and outer aluminium parts should each be at almost one temperature.
- Heat flux: look where the flux arrows "escape": screws, continuous aluminium bridges, badly modelled cavities.
- Mesh: if refining the mesh no longer changes the result, it is fine enough.
- Compare the value with catalogue values of similar profiles.
End-of-day check (15 min)
ψg
Goal
By the end of the day you will be able to calculate the ψg value of the frame-glass junction: model with real glass and spacer, subtracting the Uf and Ug contributions. About 3 hours.
1. Method (1 hour)
- This time put the real insulating glass unit in the same section: glass panes, spacer, secondary seal (butyl, silicone/polysulphide), gas fill.
- Visible glass width again bg ≥ 190 mm.
- Solve → L2Dψ.
- ψg = L2Dψ − Uf · bf − Ug · bg
Uf comes from day 4; Ug from the glass manufacturer's EN 673 value.
2. Example (45 min)
Uf = 2.55, bf = 0.08 m, Ug = 1.1, bg = 0.19 m, L2Dψ = 0.48 W/(m·K) from the program:
| Step | Calculation | Result |
|---|---|---|
| Uf · bf | 2.55 × 0.08 | 0.204 |
| Ug · bg | 1.1 × 0.19 | 0.209 |
| ψg | 0.48 − 0.204 − 0.209 | 0.067 W/(m·K) |
3. Spacers (45 min)
| Spacer | ψg tendency |
|---|---|
| Aluminium | High |
| Stainless steel | Medium |
| Warm edge (polymer, composite) | Low |
ψg also affects the internal surface temperature at the glass edge: in cold climates an aluminium spacer increases the condensation risk at the glass edge (day 6).
4. Opaque panel junction (15 min)
The same method gives ψp for the spandrel panel junction; only the real panel section is modelled instead of glass.
End-of-day check (15 min)
Ucw and condensation
Goal
By the end of the day you will be able to calculate a curtain wall module's Ucw with the component method and check condensation from the internal surface temperature. About 3.5 hours.
1. Ucw: component method (1.5 hours)
The component method of EN ISO 12631:
Ucw = (ΣAg·Ug + ΣAp·Up + ΣAf·Uf + Σlg·ψg + Σlp·ψp) / Acw
Example module 1500 × 3200 mm (Acw = 4.80 m²); areas and lengths are examples:
| Component | Quantity | U / ψ | Contribution (W/K) |
|---|---|---|---|
| Glass Ag | 3.20 m² | 1.1 | 3.520 |
| Panel Ap | 1.10 m² | 0.33 | 0.363 |
| Frame Af | 0.50 m² | 2.2 | 1.100 |
| Glass edge lg | 7.6 m | 0.067 | 0.509 |
| Panel edge lp | 4.0 m | 0.15 | 0.600 |
| Total | 6.092 | ||
| Ucw | 6.092 / 4.80 | 1.27 W/(m²·K) |
Check: Ag + Ap + Af = 3.20 + 1.10 + 0.50 = 4.80 m² ✓.
Note: although the centre of the panel is 0.33, the module average is much higher because of the edges and the frame. Reporting opaque areas as "U = 0.33" is misleading.
2. Condensation and fRsi (1.5 hours)
In cold weather, if the coldest point of the internal surface falls below the dew point, condensation forms. At 20 °C and 50 % relative humidity the dew point is ≈ 9.3 °C.
Temperature factor:
fRsi = (θsi,min − θe) / (θi − θe)
Example: θi = 20 °C, θe = −5 °C, coldest internal surface from the 2D model θsi,min = 13 °C:
fRsi = (13 − (−5)) / (20 − (−5)) = 18 / 25 = 0.72
An example criterion (e.g. DIN 4108-2 in Germany) is fRsi ≥ 0.70; this section passes. Use the criterion in the project specification. For condensation checks a larger internal surface resistance such as Rsi = 0.25 is commonly used (effect of curtains, furniture); check your standard.
3. Where is it cold? (15 min)
The coldest points are usually: the glass edge (spacer), mullion-transom junctions, anchors and brackets (3D bridges) and the slab edge. A 2D model does not fully capture corners and point bridges; critical places may need a 3D calculation.
End-of-day check (15 min)
Report
Goal
On the last day you will look at tools, reporting, common mistakes and the final exercise. About 3.5 hours.
1. Tools (45 min)
| Tool | Note |
|---|---|
| THERM (LBNL) | Free, widely used 2D thermal bridge program |
| Flixo | Commercial; quick models from DXF, 10077-2 and 12631 reports |
| Other finite element programs | Check that they solve the validation cases |
| Excel | 10077-1 and 12631 area calculations (days 2 and 6) |
Whatever program you use, solve the standard's validation cases once and keep the results: they show in the report that the program is validated.
2. Report (1 hour)
A thermal calculation report includes:
- Project, section name, profile series, revision.
- Standards and editions (EN ISO 10077-1/-2, EN ISO 12631, EN 673).
- Geometry (section drawing), materials and λ values (with sources).
- Cavity modelling and boundary conditions.
- Results: Lf2D, Uf, L2Dψ, ψg, isotherm and heat flux images.
- Uw / Ucw calculation and comparison with the code or specification.
- Condensation assessment (fRsi).
3. Common mistakes (30 min)
| Mistake | Result |
|---|---|
| bp or bg < 190 mm | Edge effect does not die out; Uf/ψ wrong |
| Solving Uf with real glass | Uf and ψ get mixed |
| Filling cavities with solid aluminium | Uf far too high |
| Drawing screws and point connections as continuous in 2D | Uf too high; the 3D effect must be handled separately |
| Using Rsi = 0.13 everywhere | Internal surface looks warmer than it is at corners |
| Measuring visible widths wrongly | Uw/Ucw wrong |