Façade calculations depend on each other: wind sizes the glass, glass and wind size the mullion, the mullion sizes the bracket. Here are five calculations done in order on one building; each link opens the calculator with the same values.

Erdal Üstünol · 18.11.2026Türkçe
  • Building: 30 m high, 40 × 20 m office in Istanbul; suburban (terrain category III).
  • Façade: capped stick curtain wall, mullion spacing 1500 mm, floor height 3600 mm, glass 1500 × 2500 mm.
  • Checked location: the worst case, corner zone A at the top floor.
  • Result: 8 toughened / 16 / 44.2 heat-strengthened glass, mullion I ≥ 550 cm⁴, bracket with 2 anchors, 18 mm joint.

1. Wind load

Basic wind velocity 28 m/s, category III, h = 30 m. The calculator gives a peak velocity pressure of qp = 1.215 kN/m² (mean velocity 27.8 m/s, turbulence 0.217). Since the element is a 3.75 m² glass pane, cpe is interpolated between cpe,10 and cpe,1.

Zonecpe (3.75 m²)Net loadDesign (×1.5)
A (corner)−1.29−1.80 kN/m²−2.71 kN/m²
B−0.93−1.37 kN/m²−2.06 kN/m²
D (windward)+0.89+1.44 kN/m²+2.16 kN/m²

Internal pressure (cpi +0.2 / −0.3) is included in the net load. All following steps use the corner suction of 1.80 kN/m²; it is a characteristic value, and each calculation applies its own safety factor. Open this step →

2. Glass thickness

1500 × 2500 mm insulating glass supported on four edges: 8 mm toughened outside, 44.2 laminated inside. In the first try the inner laminate was annealed float: the inner pane stress is 20.3 MPa against a design strength of 18.5 MPa — not enough. Switching the inner laminate to heat-strengthened raises the strength to 39.3 MPa and the glass passes:

CheckValueLimit
Outer pane stress40.6 MPa81.0 MPa
Inner pane stress20.3 MPa39.3 MPa
Deflection19.2 mm23.1 mm (short edge / 65)

Deflection governs (83%). The wind load is shared between the panes by stiffness: the 8 mm outer pane takes about 80% of it. The glass weighs 40 kg/m², 150 kg per pane, which is also needed for setting blocks and lifting equipment. Open this step →

3. Mullion deflection

The mullion hangs from each floor, span L = 3600 mm, load width 1500 mm. Line load q = 1.80 × 1.50 = 2.70 kN/m. First we try a 400 cm⁴ profile: deflection 21.1 mm against a limit of 5 + 3600/300 = 17.0 mm, and the stress of 182 MPa exceeds 145 MPa. The calculator gives the requirement: I ≥ 496 cm⁴, W ≥ 45.2 cm³.

With a deeper profile (I = 550 cm⁴, W = 52 cm³) deflection becomes 15.3 mm (90%) and stress 126 MPa (87%). If you want to keep the profile, steel reinforcement inside can cover the same need; since steel's E is three times higher, 1 cm⁴ of steel acts like about 3 cm⁴ of aluminium. The support reaction is 4.86 kN at each end and feeds the next step. Open this step →

4. Brackets and anchors

One bracket carries 1.50 × 3.60 = 5.40 m² of façade. Façade weight is taken as 60 kg/m² (glass 40 kg/m² plus profiles and other parts). The bracket is fixed to the slab edge with 2 anchors; the weight acts at 120 mm eccentricity.

QuantityValue
Weight Gk / design3.18 kN / 4.29 kN (×1.35)
Wind Wk / design9.72 kN / 14.58 kN (×1.5)
Anchor tension NEd11.58 kN ≤ 15.00 kN
Anchor shear VEd2.15 kN ≤ 12.00 kN
Interaction (βN)1.5 + (βV)1.50.75 ≤ 1

Tension comes from wind suction plus the moment of the eccentric weight. The anchor resistances here (15 and 12 kN) are only examples: real values depend on concrete class, cracked concrete and edge distances and come from the manufacturer's ETA or design software. The bracket itself and its welds are checked separately with the fillet weld and bolt calculators. Open this step →

5. Joint

The composite panel cladding at the slab edge has a panel length of 3600 mm, α = 24 × 10⁻⁶. Installed at 15 °C; surface temperature between −20 °C and +60 °C (light colour). The panel closes the joint by 3.89 mm when heated and opens it by 3.02 mm when cooled. For a sealant with ±25% movement capability:

3.89 ÷ 0.25 = 15.6 mm + 2 mm installation tolerance → 18 mm joint

Sealant depth 9 mm (width/depth 2:1), with a Ø25 mm closed-cell backer rod behind. For a dark panel use 80 °C as the upper temperature; the joint grows. Open this step →

Summary and next steps

StepInputResult
Wind28 m/s, cat. III, 30 mqp 1.215; zone A −1.80 kN/m²
Glass1500 × 2500, 1.80 kN/m²8T / 16 / 44.2 heat-strengthened, 83%
MullionL 3600, spacing 1500I ≥ 496 cm⁴ → 550 cm⁴ chosen
Bracket5.40 m², 60 kg/m²2 anchors, NEd 11.6 kN, interaction 0.75
Joint3600 mm panel, −20…+60 °C18 mm, depth 9 mm

These five calculations are preliminary sizing. In a project they are followed by structural silicone (for SSG façades), performance classes and test pressures, Ucw and condensation. The "Next step" buttons under each calculator carry the values forward.

This guide is for education and preliminary information only; regulations, standards and values may change. Consult a qualified engineer before making decisions. If you spot an error, let me know. · All guides